Designated Exempted Works

Supporting frames for air-conditioning units or light fittings

Item details

Designated Exempted Works - 13
Designated Exempted Works item no. 13
Nature of works Erection/Alteration/Removal of any supporting frame projecting from an external wall of a building
The frame is for supporting Air-conditioning unit or light fitting
Result in any additional load to any cantilevered slab No
Projection from the wall Not more than 600mm
The distance between the highest point of the frame and the roof or ground Not more than 3m
The frame is designed for Weight of an air-conditioning unit or light fitting of not more than 100kg
The frame projects over any street or common part of the building No