Minor works items - 1.47
Class I TypeAE
- Jump to
- Item details
- Submission procedure
Item details
Item no. | 1.47 |
---|---|
Item class/type | Class I TypeAE |
Nature of works | Erection/Alteration |
Location of the external metal ventilation duct or associated supporting frame |
|
Result in any additional load to any cantilevered slab | No |
If the duct or frame projects from the external wall of a building or from a solid fence wall on-grade, projection of the duct | No part of the duct or frame projects more than 750mm |
If the duct or frame is located on a balcony, verandah or canopy |
|
If the duct or frame is hung underneath the soffit of a balcony, verandah or canopy |
|
Other requirement | Not involve Designated Exempted Works item 22 or 23 or Minor Works item 2.47, 3.47 or 3.48 |
More details: See Item 1.47 Description of building works, Schedule 1 - Part 3 - Division 1, Building (Minor Works) Regulation
Submission procedure
Step 1
Owner or their agent
Appoint Prescribed Building Professional and Prescribed Registered Contractor (Class I of Type A, E)
Step 2
Prescribed Building Professionals
Submit MW01 - Notice of Commencement, documents, photos 7 days before commencement of work
Step 3
Prescribed Building Professionals
Submit MW02 - Certificate of Completion, documents, photos within 14 days after completion of work